PRODUCT SPECIFICATIONS
The TP-BC72-600 battery chargers provide up to 600W of total charging power. The battery charger is compatible with GEL/AGM type sealed lead acid batteries.
The charger has various protections for reverse current, short-circuit, over-load, over-voltage, and over-current.
There is an LED which indicates charging (Red) or battery full (Green). The unit comes with a removeable AC cord with a North American Plug.
The units are can work from 90VAC to 240VAC (selectable via switch).
Features
- 72V 600W Total Power
- Over-Voltage, Over-Current, Reverse-Current, Over-Load, Short-Circuit Protections
- Led indicator: Red=Charging, Green=Battery Full/Float Charge
- CE Certification
Applications
- Wireless Base Stations, Cellular Base Stations
- Surveillance Systems
- Battery Backup Systems
Dimensions (LxWxH)
- 216 x 120 x 76mm (8.5 x 4.75 x 3”)
Weight
- 1.95kg (4.3lb)
Technical Description
- Total Power Available (for Load and Battery charging): 600W
- Nominal Battery Voltage: 72VDC
- Battery Charge Max Current: 6A
- Battery Charger Voltage: 88.2V
- Battery Float Voltage: 82.8V
- Efficiency: >88%
- DC Output Cable: 2 Wire 14AWG ; 1.2m (48”) long cable Brown = V+, Blue = VAC Input Connector IEC C14
- AC Power Cord: IEC C13 to Nema 5-15P, 1.2m (48")
- AC Power Input: 120VAC / 240VAC , 50/60Hz
- Hi-Pot Test: 1500VAC / 10mA / 1min
- Insulation Resistance: >10MOhm, 500VDC
- Operating Temperature: -10 to +40C (14 to +104°F)
- Operating Humidity (RH): 5% to 90% (non condensing)
- Storage Temperature: -40 to +70°C (-40 to +158°F)
- Storage Humidity: 5% to 95% (non-condensing)
- Standards Compliance: CE, EN60335-1:2002 and EN60335-2-29:2002
- MTBF (Mean Time Between Failure): >50,000 hrs