null

Tycon Power Systems

Part:
TPDIN-MONITOR-WEB3

Tycon Power TPDIN-Monitor-WEB3 Remote Station Monitor and Control WEB and SNMP

$179.95
$209.95
Condition:
New

PRODUCT SPECIFICATIONS

The TPDIN-Monitor-WEB3 is a remote monitoring and control system designed for versatility. It allows remote monitoring of up to 4 voltages, 4 currents, and 2 temperatures, with control over 4 on-board relays via web or SNMP network access. Additionally, it interfaces with Tycon MPPT solar controllers for comprehensive monitoring and control of solar systems. With surge protection, data logging, and graphing capabilities, it offers historical data visualization and real-time parameter monitoring via a user-friendly web interface accessible on desktops, laptops, tablets, and smartphones. Relay control is highly flexible, with options based on various parameters, and special features like one-click cycle for device rebooting. Bi-directional current ports and external shunt support enhance battery monitoring capabilities. Removable wire terminal connectors facilitate easy troubleshooting and maintenance. User-defined labels, unique network identification, and programmable offsets ensure adaptability to specific needs. Email alerts and SNMP support enable automated remote data collection and control. A free discovery tool aids in locating units on the network, simplifying setup and management.

Technical Description

  • Voltage Measurement (DC): V1, V2, V3, V4 = 0-80VDC
  • Voltage Measurement Accuracy: +/- 0.1V
  • Current Measurement (DC): I1, I2 = 0.1A to 15A (20A Peak) using 12AWG Wire, I3 = +/-10A
  • I4 Supports External Current Shunts – Input Range: +/-25mV
  • Current Measurement Accuracy: +/- 0.1A
  • Common Mode Voltage Range: -14V to +80V
  • Temperature Measurement: T1,T2 = -40C to 125C
  • Temperature Measurement: Type T2 = Embedded, T1 = External Sensor (included)
  • Temperature Measurement Accuracy: +/- 1 degC
  • Relays: CH1, CH2 (NC); CH3, CH4 (NO) = 10A 30VDC, 125-250VAC
  • Relay Control: CH1, CH2, CH3, CH4 = Manual or Automatic based on Volts, Amps, Temperature, Ping(5 secs Interval, 3 min Holdoff) or Time
  • Power Requirements 10-57VDC Wire Terminal or 802.3af/at Class 0 PoE or 24V Passive PoE 1.5W All Relays Off, 3.5W All Relays On
  • Accessibility: Via Web Browser and SNMP
  • Data-Logger: FIFO, Max 4048 data sets, Programmable log interval
  • Data Connections: 8 Pin RJ45, 6pin RJ12 RS232/485 Interface to Tycon MPPT Solar Controllers
  • Measurement Connections: Removable Wire Terminal
  • Wire Size: 12AWG Max
  • Mounting: DIN Rail
  • MTBF: 111,199 hrs
  • Operating Temperature: -40C to +75C (-40F to 167F)
  • Humidity (RH): 0% - 90%
  • Certifications: FCC & CE

More Information

MFRPartNum:
TPDIN-Monitor-WEB3